47DV
P. 20 / 34
EM-9501-B Rev.6
PARAMETER
Note 1: All setpoints can be set and indicated regardless of alarm output options. H and L setpoints are output to the terminals with dual
alarm output option.
Note 2: Bank No. and Bank copy can be used only when Bank switching is possible via the front button controls.
Note 3: Specify setpoint and deadband in the scaled range values. Alarm is invalid when ‘ – – – – ’ is specified for the setpoint.
Note 4: All alarm setpoints are disabled (reset to ‘ – – – – ’ status) when the input type has been changed. Re-setting is required.
*
1. Selectable only at Alarm Setting Lockout Level LV0.
*
2. Trip action type setting is disregarded with Zone output.
*
3. HH and LL are reset to ‘ – – – – ’ for dual alarm output option. All setpoints are reset to ‘ – – – – ’ for no alarm output option.
FUNCTION
DEFAULT
VALUE
MAIN DISPLAY
SUB DISPLAY
Alarm output pattern
Zone
Normal
Bank No.
Bank No.
...
...
...
...
...
...
LL setpoint
LL deadband (hysteresis)
*
1
LL ON delay time
*
1
LL: ON delay time (x100 ms)
LL OFF delay time
*
1
LL: OFF delay time (x100 ms)
LL: Deadband (hysteresis) value
LL: Setpoint value
LL trip action
*
1,
*
2
LL: Hi trip
LL: Lo trip
LL coil at alarm
*
1
LL: Coil energized at alarm
LL one-shot output
*
1
L setpoint
L deadband (hysteresis)
*
1
L ON delay time
*
1
L OFF delay time
*
1
L trip action
*
1,
*
2
L coil at alarm
*
1
L one-shot output
*
1
H setpoint
H deadband (hysteresis)
*
1
H ON delay time
*
1
H OFF delay time
*
1
H trip action
*
1,
*
2
H coil at alarm
*
1
H one-shot output
*
1
HH setpoint
HH deadband (hysteresis)
*
1
HH ON delay time
*
1
HH OFF delay time
*
1
HH trip action
*
1,
*
2
HH coil at alarm
*
1
HH one-shot output
*
1
LL: One-shot output time (x100 ms)
LL: Coil de-energized at alarm
L: ON delay time (x100 ms)
L: OFF delay time (x100 ms)
L: Deadband (hysteresis) value
L: Setpoint value
L: Hi trip
L: Lo trip
L: Coil energized at alarm
L: One-shot output time (x100 ms)
L: Coil de-energized at alarm
H: ON delay time (x100 ms)
H: OFF delay time (x100 ms)
H: Deadband (hysteresis) value
H: Setpoint value
H: Hi trip
H: Lo trip
H: Coil energized at alarm
H: One-shot output time (x100 ms)
H: Coil de-energized at alarm
HH: ON delay time (x100 ms)
HH: OFF delay time (x100 ms)
HH: Deadband (hysteresis) value
HH: Setpoint value
HH: Hi trip
HH: Lo trip
HH: Coil energized at alarm
HH: One-shot output time (x100 ms)
HH: Coil de-energized at alarm
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
P ON delay time
*
1
P: ON delay time (x100 ms)
P OFF delay time
*
1
P: OFF delay time (x100 ms)
P coil at alarm
*
1
P: Coil energized at alarm
P one-shot output
*
1
P: One-shot output time (x100 ms)
P: Coil de-energized at alarm
Bank copy
No copying
Copy current bank value to all banks
Display flashing at alarm
Flashing in approx. 1.0 sec. intervals
No flashing
Flashing in approx. 0.3 sec. intervals
Flashing in approx. 0.5 sec. intervals
/
/
/
/
*
3
*
3
*
3
*
3
■
PARAMETERS LIST