47DV
P. 27 / 34
EM-9501-B Rev.6
■
FUNCTIONS, TERMINOLOGY
• Event trigger mode
All logical inputs in the following are in the negative logic (ON at Low signal, unchangeable).
HOLD
RESET
*2
*3
Hold
TIMING
RESET
*1. Scaling error
*2. Measuring
*3. Not measuring
*1. Scaling error
*1. Scaling error
*2. Measuring
*1. Scaling error
*2. Measuring
*1. Scaling error
*2. Measuring
Display
reading
TIMING
RESET
TIMING
RESET
TIMING
RESET
Scaling error range
P1
B2
B1
P2 – B2
0
P2
P1 – B1
TIMING signal
While HOLD signal is ON, the display reading is held at the measured value at
the falling edge of HOLD signal, and TIMING, S-TMR and ZERO signals are in-
valid.
HOLD signal
During Scaling Error, data measuring continues. However the display shows
Scaling Error. If HOLD signal turns ON during Scaling Error and is maintained
after the Scaling Error is canceled, the display reading changes to the
measured value at the falling edge of HOLD signal.
Scaling Error
RESET signal
Proportional to the display reading. When RESET signal is ON, the value is
0%.
DC output
Data is measured at the falling edge of TIMING signal.
While HOLD signal is ON, the display reading is held at the measured value at
the falling edge of HOLD signal, and TIMING, S-TMR and ZERO signals are in-
valid.
Stops data measuring.
Resets the measured data and TIMING signal is invalid.
Proportional to the display reading. For no measured data, the value is 0%.
While TIMING signal is ON, the maximum value within the period is measured
and stored.
While HOLD signal is ON, the display reading is held at the last measured val-
ue at the falling edge of HOLD signal, and TIMING, S-TMR and ZERO signals
are invalid.
Stops data measuring.
Resets the measured data and TIMING signal is invalid.
Proportional to the display reading. For no measured data, the value is 0%.
While TIMING signal is ON, the minimum value within the period is measured
and stored.
While HOLD signal is ON, the display reading is held at the last measured val-
ue at the falling edge of HOLD signal, and TIMING, S-TMR and ZERO signals
are invalid.
Resets the measured data and TIMING signal is invalid.
Proportional to the display reading. For no measured data, the value is 0%.
While TIMING signal is ON, the difference between maximum and minimum val-
ue within the period is measured and stored.
While HOLD signal is ON, the display reading is held at the last measured val-
ue at the falling edge of HOLD signal, and TIMING, S-TMR and ZERO signals
are invalid.
Stops data measuring.
Resets the measured data and TIMING signal is invalid.
Proportional to the display reading. For no measured data, the value is 0%.
*1
*2
*2
*1
*2
*2
*1
*2
*2
*1
Display
reading
Display
reading
Display
reading
Scaling error range
Scaling error range
Scaling error range
Scaling error range
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
Hold
*2
Not measuring
Not measuring
Not measuring
Not measuring
Not measuring
Not measuring
Not measuring
*1
*2
TIMING within RESET: Invalid
Not measured if TIMING rises during
a scaling error
TIMING within RESET: Invalid
Not measured if a scaling error occurs
while TIMING is ON
TIMING within RESET: Invalid
TIMING within RESET: Invalid
Not measured if a scaling error occurs
while TIMING is ON
Not measured if a scaling error occurs
while TIMING is ON
Normal Mode
Sampling Hold Mode
Peak Hold Mode
Valley (Bottom) Hold Mode
Peak-to-peak Hold Mode
TIMING signal
HOLD signal
Scaling Error
RESET signal
DC output
TIMING signal
HOLD signal
Scaling Error
RESET signal
DC output
DC output
DC output
RESET signal
RESET signal
Scaling Error
HOLD signal
TIMING signal
TIMING signal
HOLD signal
Scaling Error
The status indicator turns on. However, the signal is invalid.
Resets the measured data.
Stops data measuring.
Not measuring