47DV
P. 33 / 34
EM-9501-B Rev.6
Shift
Shift
Scale/
Alarm/
Device Address
Measuring Mode
Baud Rate
Parity Bit
Long Register
1200 / 2400 / 4800
9600 / 19200 / 38400
NONE / ODD / EVEN
NORMAL / SWAP
Hold down Alarm/ or Scale/ button
for
≥
1 second
Shift
Alarm/
Scale/
Alarm/
Shift
Scale/
Alarm/
Modbus Setting Mode
Alarm/
001...247
Alarm/
Hold down Alarm/ + Shift button
for
≥
3 seconds
A
T1.5 Timer
01...60
Shift
Alarm/
Scale/
Alarm/
Scale/
T3.5 Timer
01...60
Shift
Alarm/
Scale/
Alarm/
Scale/
Scale/
Scale/
Scale/
Scale/
Set value
Setting Parameters
A
Alarm/
Alarm/
Stop Bit
1 / 2
Shift
Scale/
Scale/
Alarm/
Alarm/
Modbus Setting Mode is usable only with RS-485/Modbus RTU interface option.
PARAMETER
FUNCTION
DEFAULT
VALUE
MAIN DISPLAY
SUB DISPLAY
...
...
...
T1.5 timer
T3.5 timer
Protocol operating timer, t3.5
Protocol operating timer, t1.5
Baud rate
1200 bps
2400 bps
4800 bps
9600 bps
19200 bps
Parity bit
Stop bit
None
Odd
Even
1 bit
2 bits
Long register
Modbus setting changes are enabled only after the the power supply has been turned off and on.
Low-digit word at lower address
High-digit word at lower address
38400 bps
Device address
Device address
MODBUS SETTING MODE
■
FLOWCHART
■
PARAMETERS LIST