206
47DR OPERATING MANUAL EM-9509-B Rev.7
5
Press Shift button to shift the display into the setting standby
mode. Press Shift and Up buttons to set the input compensa-
tion A compensation value.
• The sixth digit starts blinking, to which you can apply changes.
• Set within the range of -999.99 to 9999.99.
*
Set a positive value to set a higher value than the present one. Set a negative value to set a lower value.
NOTE
Set to 2 decimal places regardless of the decimal point position setting.
6
Press Alarm/
↓
button to register the value and to go to the
input compensation B input value setting.
• The input compensation A compensation value is registered.
• The input compensation B input value is indicated.
• The SD indicates ‘CR-B IN’.
7
Set the input compensation B input value and input compen-
sation B compensation value.
• Repeat the steps 2 to 6 to set the input compensation B input
value and input compensation B compensation value.
*
The SD indicates ‘CR-B CR’ with input compensation B compensation value setting.
8
Hold down Alarm/
↓
or Init/
↑
button for 3 seconds or more to return to Measuring Mode.
Blinking