47DR OPERATING MANUAL EM-9509-B Rev.7
9.1 ANALOG OUTPUT TYPE
9.1.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the settings.
1
Hold down Init/
↑
button for 3 seconds or more to move on to
Initial Setting Mode.
• The input type is indicated.
• The SD indicates ‘RTTYPE’.
2
Press Alarm/
↓
or Init/
↑
button to go to the analog output type
setting.
• The analog output type is indicated.
• The SD indicates ‘ANG TYP’.
3
Press Shift and Up buttons to select the analog output type.
• Select one among ‘4-20MA’, ‘0-5V’, ‘5V’, ‘10V’ and ‘0-20MA’.
4
Press Alarm/
↓
or Init/
↑
button to apply the new setting.
• And the next parameter setting is indicated.
NOTE
• Press Alarm/
↓
button, and the analog output function mode will be indicated (‘ANG VAL’ on the SD).
• Press Init/
↑
button, and the bargraph upper limit will be indicated (‘BAR-H’ on the SD), or the bargraph type will be indi-
cated (‘BAR-GRH’ on the SD) with the bargraph type set to “no bargraph”.
2,4
1,2,
4
3
3
Blinking