65
47DR OPERATING MANUAL EM-9509-B Rev.7
■
SETTING RANGE OF BARGRAPH LOWER AND UPPER LIMITS
The bargraph lower and upper limits can be set within the range of -999.99 to 9999.99.
The default values per input type are as shown in the following tables.
The default values are 0000.00 for bargraph lower limit, and 0100.00 for upper limit.
■
TEMPERATURE UNIT: °C
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPE 4
Pt 100 (JIS ’97, IEC)
-230.00 to +880.00
-200.00 to +850.00
Bargraph lower limit:
Bargraph upper limit:
TYPE 5
Pt 50 Ω (JIS ’81)
-230.00 to +679.00
-200.00 to +649.00
Bargraph lower limit:
Bargraph upper limit:
TYPE 7
Pt 1000
-230.00 to +880.00
-200.00 to +850.00
Bargraph lower limit:
Bargraph upper limit:
TYPE 1
JPt 100 (JIS ’89)
-230.00 to +530.00
-200.00 to +500.00
Bargraph lower limit:
Bargraph upper limit:
TYPE 3
Pt 100 (JIS ’89)
-230.00 to +680.00
-200.00 to +650.00
Bargraph lower limit:
Bargraph upper limit:
■
TEMPERATURE UNIT: °F
MAIN DISPLAY
FUNCTION
USABLE RANGE
CONFORMANCE RANGE
DEFAULT VALUE
TYPE 4
Pt 100 (JIS ’97, IEC)
-382.0 to +1616.0
-328.0 to +1562.0
Bargraph lower limit:
Bargraph upper limit:
TYPE 5
Pt 50 Ω (JIS ’81)
-382.0 to +1254.2
-328.0 to +1200.2
Bargraph lower limit:
Bargraph upper limit:
TYPE 7
Pt 1000
-382.0 to +1616.0
-328.0 to +1562.0
Bargraph lower limit:
Bargraph upper limit:
TYPE 1
JPt 100 (JIS ’89)
-382.0 to +986.0
-328.0 to +932.0
Bargraph lower limit:
Bargraph upper limit:
TYPE 3
Pt 100 (JIS ’89)
-382.0 to +1256.0
-328.0 to +1202.0
Bargraph lower limit:
Bargraph upper limit:
IMPORTANT
• The bargraph lower and upper limits are returned to the default values per input type when the input type has been
changed.
• The bargraph lower and upper limits can be set arbitrarily. However it is recommended to use them within the usable
range.