47DR OPERATING MANUAL EM-9509-B Rev.7
■
INFRARED COMMUNICATION
Perform infrared communication in the following procedure.
Refer to 47DCFG PC Configurator Software Users Manual for details of configuration.
(1) Move on to Infrared Communication Mode.
(2) Face the infrared interface of the unit to the send/receive window of the COP-IRU connected to the PC with the
47DCFG installed within 1 meter.
(3) Manipulate 47DCFG files. The main display blinks first and then turns on in downloading.
(4) Quit Infrared Communication Mode when the operation is finished.
IMPORTANT
• The infrared communication cannot be performed when the COM port of the COP-IRU connected to a PC is set incor-
rectly.
• Communication can be affected by sunlight, fluorescent lightings employing inverter technology and so forth. Try at a
shorter distance if communication is not established.
• The COP-IRU can communicate with single panel meter only. Do not turn more than one panel meter on to Infrared
Communication Mode.
NOTE
• PC configuration via infrared communication may take time. It is convenient to fix the COP-IRU with L Type Holder
(optional).
Panel
L Type Holder
COP
-
IRU
• Reading and writing parameters using the 47DCFG are available also via Modbus communication. In downloading, the
main display indicates ‘MODBUS’. Refer to 47DCFG PC Configurator Software Users Manual for details.
max.1 meter
Infrared Communication
Adaptor (model: COP-IRU)
Digital Panel Meter
(model: 47Dx)
Digital Panel Meter
(model: 47Dx)
Infrared Communication
Adaptor (model: COP-IRU)
Infrared Interface
Send/Receive Window