Equipment and Cable Installation for Metropolis
®
DMXplore Shelf (Wall-Mount)
Office Alarm Cable Installation
1 - 3 4
365-372-334 R2.0
Issue 4, November 2004
Procedure
Step 1
Obtain the office alarm cable per Table 1-9, Office Alarm Cable
Assemblies (page 1-33). Connect the office alarm cables to the
ALARM terminal block in the lower left hand corner of the access
panel. See Figure 1-14, Office Alarm Cable Connections (page 1-35)
Important!
The recommended wire strip length for cables being
connected to the alarm block is 11mm.
Table 1-10
Office Alarm Connections
Pin#
Color
Name
Designation
1
2
BL
BL/W
CR/MJ
CR/MJ Visual -
RYCRMJV1
3
4
O
O/W
CR/MJ A
CR/MJ Audible -
RYCRMJA1
5
6
G
G/W
MN/ABN
MN/ABN Visual -
RYMNABNV1
7
8
BR
BR/W
MN/ABN A
MN/ABN Audible -
RYMNABNA1
Notes:
1. The SYSCTL circuit pack reports office alarms.