The pH Sensor Reading Is Constantly Over-range or Under-range
Ensure that the sensor and temperature input is correctly connected (See page 47) and that the
sensor is not faulty or damaged.
Check the temperature compensation state (See page 107). If the compensation is set to “Manual”
check that the fixed temperature is at the correct level. If the compensation is “Automatic” check
that the temperature reading on the main display is correct.
The pH Sensor Reading Is Incorrect
Check that no error messages are being displayed. Check that the sensor cable has been correctly
connected (See page 47).
Check that the Temperature reading is correct.
Check the instrument calibration using a pH simulator, Adjust the pH calibration if necessary (See
page 125).
Use another instrument to check the sensor.
The pH Sensor Is Not Functioning Correctly
Check that the sensor glass is not broken or cracked.
Check the reference probe KCl (where applicable) for leakage or contamination.
Ensure all probe protective caps have been removed.
Check that any junction boxes used are correctly connected.
Check that a suitable high impedance, low noise cable has been used.
Check for damaged or broken cables.
Check for damp, grease, or liquids near connectors, junction boxes, or terminations.
Where extension cables have been used, try connecting the sensor directly to the instrument.
The Temperature Reading Is Incorrect
Check that the temperature sensor is correctly attached (See Installation Section).
Check that the temperature sensor type is correctly selected in the Sensor Setup menu.
Where practical check the temperature sensor resistance against the table on page 183.
Current Output Is Incorrect or Noisy
Check that the maximum load for the current loop has not been exceeded. (750
).
Check that the terminals have been wired correctly.
Check that the cable screen is attached to Earth at one end and that the cable does not pass too
close to a power cable.
Check that he current output has been configured properly.
Relays Appear to Malfunction
Check that the controller’s sensors are “On-Line” in the Sensor Setup menu.
Check that the relay configuration is correct.
Ensure that the relays are connected properly see Installation section.
Check that the instrument input cables are not picking up excessive noise.
Check that the front panel fuses are in working condition (See page 31).
Instrument display appears to malfunction
Switch the instrument power off and on again.
Check that the display back-light is on, indicating power is reaching the unit.
See that it displays meaningful text (Issue number etc.) in its start-up sequence, indicating
processing activity.
Summary of Contents for MTD75
Page 1: ...MTD75 Cooling Tower Controller Operation Guide ...
Page 2: ......
Page 5: ...Preface MTD75 Operation Guide 3 Declaration of Conformity ...
Page 6: ...Preface 4 MTD75 Operation Guide ...
Page 12: ...Introduction 10 MTD75 Operation Guide Introduction MXD75 Termination Overview ...
Page 29: ...Installation MTD75 Operation Guide 27 Installation Horizontal Mounting Vertical Mounting ...
Page 30: ...Installation 28 MTD75 Operation Guide Installation Blank ...
Page 72: ...Biocide A 70 MTD75 Operation Guide Biocide A BLANK ...
Page 74: ...Biocide B 72 MTD75 Operation Guide Biocide B BLANK ...
Page 88: ...Inhibitor 86 MTD75 Operation Guide Inhibitor BLANK ...
Page 98: ...pH Control 96 MTD75 Operation Guide pH Control BLANK ...
Page 100: ...Alarm Relay 98 MTD75 Operation Guide Alarm Relay BLANK ...
Page 108: ...Electrodeless Conductivity Setup 106 MTD75 Operation Guide ECS Setup BLANK ...
Page 112: ...pH Input Setup 110 MTD75 Operation Guide pH Setup BLANK ...
Page 118: ...Redox Calibration 116 MTD75 Operation Guide Redox Calibration BLANK ...
Page 140: ...pH Calibration 138 MTD75 Operation Guide pH Calibration BLANK ...
Page 142: ...Calibration Reset 140 MTD75 Operation Guide Calibration Reset BLANK ...
Page 148: ...Current Outputs 146 MTD75 Operation Guide Current Outputs BLANK ...
Page 152: ...Digital Inputs 150 MTD75 Operation Guide Digital Inputs BLANK ...
Page 158: ...Configuration 156 MTD75 Operation Guide Configuration BLANK ...
Page 160: ...Update Software 158 MTD75 Operation Guide Update Software BLANK ...
Page 164: ...Save Restore Reset 162 MTD75 Operation Guide Save Restore Reset BLANK ...
Page 166: ...Error Messages 164 MTD75 Operation Guide Error Messages BLANK ...
Page 172: ...Modbus RS485 170 MTD75 Operation Guide Modbus RS485 BLANK ...
Page 184: ...Data Logging 182 MTD75 Operation Guide Data Logging BLANK ...
Page 246: ...Appendix F 244 MTD75 Operation Guide Appendix F Blank ...
Page 254: ...Appendix G 252 MTD75 Operation Guide Appendix G BLANK ...
Page 260: ...Notes 258 MTD75 Operation Guide ...
Page 261: ...Notes MTD75 Operation Guide 259 ...
Page 265: ......