Configuration
MTD75 Operation Guide
- 153 -
Configuratio
n
Water Counter Reset
Reset the total water counter to zero.
/
– Select Option
EXIT
– Return to Main Menu
– Enter Option
Water Meter Timeout
Provision has been made to generate an alarm
condition if the water meter input pulses stop or
become very slow, which may indicate problems
with the water flow into the cooling tower.
Setting the timer to 00:00 will disable the alarm.
/
– Increase / Decrease Digit
– Select Next Digit
EXIT
– Cancel
– Save Value
If the time between incoming pulses is greater than
the set time, the unit will activate the alarm. The
controller will display a warning message on the
main display when the timer expires.
The water meter alarm can be cancelled by pressing
the “ACK” button on the front screen and selecting
“Water Meter Alarm”
This timeout can also be used to trigger the alarm
relay to indicate to external processes that the water
flow has stopped.
/
– Select Option
EXIT
– Cancel
– Save Selection
Summary of Contents for MTD75
Page 1: ...MTD75 Cooling Tower Controller Operation Guide ...
Page 2: ......
Page 5: ...Preface MTD75 Operation Guide 3 Declaration of Conformity ...
Page 6: ...Preface 4 MTD75 Operation Guide ...
Page 12: ...Introduction 10 MTD75 Operation Guide Introduction MXD75 Termination Overview ...
Page 29: ...Installation MTD75 Operation Guide 27 Installation Horizontal Mounting Vertical Mounting ...
Page 30: ...Installation 28 MTD75 Operation Guide Installation Blank ...
Page 72: ...Biocide A 70 MTD75 Operation Guide Biocide A BLANK ...
Page 74: ...Biocide B 72 MTD75 Operation Guide Biocide B BLANK ...
Page 88: ...Inhibitor 86 MTD75 Operation Guide Inhibitor BLANK ...
Page 98: ...pH Control 96 MTD75 Operation Guide pH Control BLANK ...
Page 100: ...Alarm Relay 98 MTD75 Operation Guide Alarm Relay BLANK ...
Page 108: ...Electrodeless Conductivity Setup 106 MTD75 Operation Guide ECS Setup BLANK ...
Page 112: ...pH Input Setup 110 MTD75 Operation Guide pH Setup BLANK ...
Page 118: ...Redox Calibration 116 MTD75 Operation Guide Redox Calibration BLANK ...
Page 140: ...pH Calibration 138 MTD75 Operation Guide pH Calibration BLANK ...
Page 142: ...Calibration Reset 140 MTD75 Operation Guide Calibration Reset BLANK ...
Page 148: ...Current Outputs 146 MTD75 Operation Guide Current Outputs BLANK ...
Page 152: ...Digital Inputs 150 MTD75 Operation Guide Digital Inputs BLANK ...
Page 158: ...Configuration 156 MTD75 Operation Guide Configuration BLANK ...
Page 160: ...Update Software 158 MTD75 Operation Guide Update Software BLANK ...
Page 164: ...Save Restore Reset 162 MTD75 Operation Guide Save Restore Reset BLANK ...
Page 166: ...Error Messages 164 MTD75 Operation Guide Error Messages BLANK ...
Page 172: ...Modbus RS485 170 MTD75 Operation Guide Modbus RS485 BLANK ...
Page 184: ...Data Logging 182 MTD75 Operation Guide Data Logging BLANK ...
Page 246: ...Appendix F 244 MTD75 Operation Guide Appendix F Blank ...
Page 254: ...Appendix G 252 MTD75 Operation Guide Appendix G BLANK ...
Page 260: ...Notes 258 MTD75 Operation Guide ...
Page 261: ...Notes MTD75 Operation Guide 259 ...
Page 265: ......