pH Calibration
- 134 -
MTD75 Operation Guide
pH Cali
bration
Place Electrode In 4pH Buffer
Place the electrode in the 4pH buffer and press enter
to begin sampling.
Note. If the electrode is new, pressing the “new”
button will reset the existing offset and slope and
add a “new electrode” entry in the calibration history.
NEW
– Register New Electrode
EXIT
– Exit Calibration Without Saving
– Initiate 4pH Calibration
Calibration Error
If no problem has been detected the instrument will
automatically progress to the next calibration point.
If it has encountered a problem this screen will
appear.
Check that the electrode is connected correctly and
that the correct buffer has been used. Then press
“Retry” to repeat the calibration.
PREV
– Go to Previous Calibration Point
SKIP
– Skip to Next Calibration Point
EXIT
– Exit Calibration Without Saving
– Initiate Calibration
Place Electrode In 9pH Buffer
Place the electrode in the 9pH buffer and press enter
to begin sampling.
If the calibration has been completed successfully the
instrument will return back to the main calibration
menu.
EXIT
– Exit Calibration Without Saving
– Initiate 9pH Calibration
Offset and Slope
Once back in the main menu the calculated offset
and slope values being used by the instrument will
be displayed.
Lower down in the calibration menu the instrument
will also display the sensor condition calculated from
the span and offset values. See page 130 for more
information.
Summary of Contents for MTD75
Page 1: ...MTD75 Cooling Tower Controller Operation Guide ...
Page 2: ......
Page 5: ...Preface MTD75 Operation Guide 3 Declaration of Conformity ...
Page 6: ...Preface 4 MTD75 Operation Guide ...
Page 12: ...Introduction 10 MTD75 Operation Guide Introduction MXD75 Termination Overview ...
Page 29: ...Installation MTD75 Operation Guide 27 Installation Horizontal Mounting Vertical Mounting ...
Page 30: ...Installation 28 MTD75 Operation Guide Installation Blank ...
Page 72: ...Biocide A 70 MTD75 Operation Guide Biocide A BLANK ...
Page 74: ...Biocide B 72 MTD75 Operation Guide Biocide B BLANK ...
Page 88: ...Inhibitor 86 MTD75 Operation Guide Inhibitor BLANK ...
Page 98: ...pH Control 96 MTD75 Operation Guide pH Control BLANK ...
Page 100: ...Alarm Relay 98 MTD75 Operation Guide Alarm Relay BLANK ...
Page 108: ...Electrodeless Conductivity Setup 106 MTD75 Operation Guide ECS Setup BLANK ...
Page 112: ...pH Input Setup 110 MTD75 Operation Guide pH Setup BLANK ...
Page 118: ...Redox Calibration 116 MTD75 Operation Guide Redox Calibration BLANK ...
Page 140: ...pH Calibration 138 MTD75 Operation Guide pH Calibration BLANK ...
Page 142: ...Calibration Reset 140 MTD75 Operation Guide Calibration Reset BLANK ...
Page 148: ...Current Outputs 146 MTD75 Operation Guide Current Outputs BLANK ...
Page 152: ...Digital Inputs 150 MTD75 Operation Guide Digital Inputs BLANK ...
Page 158: ...Configuration 156 MTD75 Operation Guide Configuration BLANK ...
Page 160: ...Update Software 158 MTD75 Operation Guide Update Software BLANK ...
Page 164: ...Save Restore Reset 162 MTD75 Operation Guide Save Restore Reset BLANK ...
Page 166: ...Error Messages 164 MTD75 Operation Guide Error Messages BLANK ...
Page 172: ...Modbus RS485 170 MTD75 Operation Guide Modbus RS485 BLANK ...
Page 184: ...Data Logging 182 MTD75 Operation Guide Data Logging BLANK ...
Page 246: ...Appendix F 244 MTD75 Operation Guide Appendix F Blank ...
Page 254: ...Appendix G 252 MTD75 Operation Guide Appendix G BLANK ...
Page 260: ...Notes 258 MTD75 Operation Guide ...
Page 261: ...Notes MTD75 Operation Guide 259 ...
Page 265: ......