Chapter 3 Installation and Test Operation
3-5
3) Pnet termination
- Connector
<Terminal connection> <Branch connection>
4) General notices
(1) Termination treatment of vertical section is needed.
(2) In case that the distance is far between stations, it is possible to extend the segment through
repeater(max. 9 repeater, 10 segment), available to connect 32 stations per segment(include
repeater), max. 126 stations. (Repeater does not have station no.) The extended segment
having no station is available.
(3) Shield shall be connected to the housing of connector.
(4) Use the special connector having the inductor inside.
(5) Spur Line is not allowed to use.
(6) If the ground potential difference between stations is big, a great amount of current may flow
through the shield. In this case, install the cable to make the ground potential difference equal
separately. For high speed more than 1.5Mbps, special cares should be taken.
(7) In case of 12Mbps, keep the distance more than 1m between stations.
5) Termination treatment
(1) Each segment should do the termination treatment for both ends. If there are several segments,
it is required to do the termination treatment for each segment.
(2) Termination is available to turn on/off by the switch of special connector.
(3) If possible, install the master at the end of one side.
Summary of Contents for 47200001
Page 15: ...Table of Content 14 ...
Page 51: ...Chapter 5 Communication Program 5 16 ...
Page 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Page 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Page 73: ...Chapter 6 SyCon Setting 6 22 ...
Page 99: ...Chapter 7 N Configurator Setting 7 26 ...
Page 115: ...Chapter 8 High speed Link 8 16 ...
Page 127: ...Chapter 9 P2P 9 12 ...
Page 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Page 173: ...Chapter 10 Program Example 10 46 ...
Page 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Page 185: ...Chapter 11 Troubleshooting 11 12 ...
Page 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Page 199: ...Warranty and Environment Policy 2 ...