Chapter 9 P2P
9-9
9.5 P2P Information
After set the driver of communication module, P2P diagnosis shows status of service and
information about communication program. User can check the P2P service with variable monitor of
monitor menu or diagnosis system.
(1) Variable monitor
Variable monitor is one of diagnosis function with flag monitor of XG5000. Select [Variable
Monitor] on the [View] menu, then [Figure 9.5.1] will be open. Register the flags which are
going to monitoring at variable monitor window. _P2PxNDR[n], _P2PxERR[n],
_P2PxSTATUS[n], _P2PxSVCCNT[n], _P2PxERRCNT[n] are array type flags, so user has
to select the number of array. The number of array means the block in the parameter.
Device
Keyword
Type
Detail
Description
%LX10000 _P2P1_NDR00
Bit
P2P parameter No.1, block
No.00
service
complete
normally
P2P parameter No.1, block No.0
service complete normally
%LX10001 _P2P1_ERR00
Bit
P2P parameter No.1, block
No.00
service
complete
abnormally
P2P parameter No.1, block No.0
service complete abnormally
%LW626
_P2P1_STATUS00 Word
Error code if P2P parameter
No.1, block No.00 service
complete abnormally
Error code displayed if P2P
parameter
No.1,
block
No.0
service complete abnormally
%LW627
_P2P1_SVCCNT00 DWord
P2P parameter No.1, block
No.00
service
normal
execution times
P2P parameter No.1, block No.0
service normal execution times
displayed
%LW\629 _P2P1_ERRCNT00 DWord
P2P parameter No.1, block
No.00
service
abnormal
execution times
P2P parameter No.1, block No.0
service abnormal execution times
displayed
[Table 9.5.1] P2P Information feature
[Figure 9.5.1] P2P variable monitor window
Summary of Contents for 47200001
Page 15: ...Table of Content 14 ...
Page 51: ...Chapter 5 Communication Program 5 16 ...
Page 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Page 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Page 73: ...Chapter 6 SyCon Setting 6 22 ...
Page 99: ...Chapter 7 N Configurator Setting 7 26 ...
Page 115: ...Chapter 8 High speed Link 8 16 ...
Page 127: ...Chapter 9 P2P 9 12 ...
Page 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Page 173: ...Chapter 10 Program Example 10 46 ...
Page 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Page 185: ...Chapter 11 Troubleshooting 11 12 ...
Page 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Page 199: ...Warranty and Environment Policy 2 ...