Chapter 2 Specifications
2-4
(2) Structure of XGL-PMEC
LED
Status
LED description
RUN
On
Normal
Completion of initialization
Off
Error
Occurrence of error
I/F
Blink
Normal
Normal status of CPU module and interface
Off
Error
Error of CPU module and interface
HS
On
Normal
Service is normal status when High-speed link enabled
Blink
Stand by
Communication break status between Pnet I/F module and slave when
downloading by N Configurator
Off
Error
High-speed link service error occurred when High-speed link is enabled
P-RUN
On
Under
communication Normal communication between the Pnet I/F module and slave
Blink
Under
communication Clear communication between the Pnet I/F module and slave (I/O data 0)
On
Communication
stop
Communication stop status between the Pnet I/F module and slave
STATUS
On
Error
System error
Blink
Auto-scan
System auto-scan mode
Off
Normal
System normal
ERR
On
Error
Bus error (line short, different communication speed, and etc.)
Blink
Error
There is disconnection during communicating with the slave module
Off
Normal
Normal status
CFG
On
Error
There is no Configuration Setting in the Pnet I/F module
Blink
Normal
Downloading or uploading the Configuration Setting
Off
Normal
A Pnet I/F module is configured normally
[Table 2.3.2] LED Display of XGL-PMEC
◀
LED display
◀
Firmware Download Port
◀
Connection area of communication cable
◀
Designation area
Summary of Contents for 47200001
Page 15: ...Table of Content 14 ...
Page 51: ...Chapter 5 Communication Program 5 16 ...
Page 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Page 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Page 73: ...Chapter 6 SyCon Setting 6 22 ...
Page 99: ...Chapter 7 N Configurator Setting 7 26 ...
Page 115: ...Chapter 8 High speed Link 8 16 ...
Page 127: ...Chapter 9 P2P 9 12 ...
Page 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Page 173: ...Chapter 10 Program Example 10 46 ...
Page 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Page 185: ...Chapter 11 Troubleshooting 11 12 ...
Page 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Page 199: ...Warranty and Environment Policy 2 ...