Chapter 9 P2P
9-7
7) Setting of P2P block
Set the P2P function, condition flag, data type, no. of variable, destination station, destination station
number, variable setting contents in P2P
[Figure 9.4.5] Setting of P2P block
Items
Description
Index
0~63 P2P setting blocks are available
P2P function
Data WRITE/READ or DIAGNOSTIC
Condition flag
Trigger of sending communication frame
Data type
Only [Byte] unit is available with P2P
No. of variable
It is fixed as 1
Destination station Check to appoint the destination station or not
Destination station
number
Set the station number of slave
Setting
Read area Data address of sending data
Save area Data address of receiving data
Slot
Slot of slave module (DPV1 specification)
Index
Index of slave module (DPV1 specification)
Data size
Size of data that is going to communicate
Variable setting
contents
This field shows the contents that user has set
[Table 9.4.4] P2P block setting
Remark
P2P function
1) WRITE function; writes the data of master to arbitrary address of slave when the condition flag
has been turned on
2) READ function; reads the arbitrary address of slave and saves to set area of master when the
condition flag has been turned on
3) DIAGNOSTIC function; reads the diagnostic information of P2P
Summary of Contents for 47200001
Page 15: ...Table of Content 14 ...
Page 51: ...Chapter 5 Communication Program 5 16 ...
Page 55: ...Chapter 6 SyCon Setting 6 4 Select Yes 5 Configuration Setup Select Next ...
Page 57: ...Chapter 6 SyCon Setting 6 6 3 Setup complete 6 Installed contents 1 Installed file ...
Page 73: ...Chapter 6 SyCon Setting 6 22 ...
Page 99: ...Chapter 7 N Configurator Setting 7 26 ...
Page 115: ...Chapter 8 High speed Link 8 16 ...
Page 127: ...Chapter 9 P2P 9 12 ...
Page 154: ...Chapter 10 Program Example 10 27 Figure 10 2 24 Link Enable High speed link P2P ...
Page 173: ...Chapter 10 Program Example 10 46 ...
Page 183: ...Chapter 11 Troubleshooting 11 10 11 4 3 XG5000 abnormal connection ...
Page 185: ...Chapter 11 Troubleshooting 11 12 ...
Page 197: ...Appendix A 8 A 3 Dimensions XGL PMEA B C have same dimensions Unit mm ...
Page 199: ...Warranty and Environment Policy 2 ...