L-INX User Manual
223
LOYTEC
Version 4.0
LOYTEC electronics GmbH
5.
Click on the
Create Device
button. This creates the M-Bus device and adds it to the
device list on the left hand side of the dialog.
6.
When a device is selected the device information is displayed in the appropriate fields
on the right hand side of the dialog. The information can be changed in the fields. Press
the
Update Device
button to store the changes.
7.
If a device has to be deleted select the device and press the
Remove Device
button.
To Add an M-Bus Device Manually Using the Scan Device Information
1.
Enter the address of the device which has to be scanned.
2.
Press the
Scan Device Information
button. If the device is found in the network, the
device properties are filled.
3.
Enter a name for the M-Bus device in the
Device Name
field. If no name is specified
the name is created automatically as described in section 10.7.1 from the M-Bus data
the device sends back.
4.
Enter a device address in the
Device Address
field. If more devices with the same
properties have to be created using subsequent addresses, the end address can be
specified in the input field on the right hand side of the Device Address field.
5.
Select a device Baud rate from the combo box.
6.
Press the
Create Device
Button to add the number of devices.
To Add an M-Bus Device Manually Using a Template
1.
Enter a name for the M-Bus device in the
Device Name
field. If no name is specified
the name is created automatically as described in section 10.7.1 from the M-Bus data
the device sends back.
2.
Enter a device address in the
Device Address
field. If more devices with the same
properties have to be created using subsequent addresses the end address can be
specified in the input field on the right hand side of the
Device Address
field.
3.
Click on the
Create From Template
button. This opens the
Import M-Bus Device
Template
dialog shown in Figure 174.