Figure 49: CEA-852 channel membership list.
The device status information is indicated with descriptive icons of different colors. The
description for the different status indicators is shown in Table 8. The
Flags
column
indicates with an
A
that the device is an auto member.
Click on the
Edit
button to change the device name, IP address, and port number for this
device. Click
Edit
on a NAT router to change the NAT router address. The
Stats
button
retrieves the statistics summary page from the client device.
Icon
Status
Description
registered
The CEA-852 device has been successfully registered
with the IP-852 channel and is fully functional.
unregistered
The CEA-852 device has never been registered with
the IP-852 channel.
not contacted
The CEA-852 device has not been contacted since
the configuration server has started.
not
responding
The CEA-852 device has been registered but is not
responding at the moment.
disabled
The CEA-852 device has been disabled on the
channel (or rejected).
No extended
NAT
The CEA-852 device does not support the extended
NAT mode. This device is disabled.
Table 8: Possible Communication Problems in the Configuration Server.
4.2.11 BACnet Configuration
Figure 50 shows the BACnet device configuration page. This configuration page allows
setting the
Device ID
, which is the instance part of the Object_Identifier property of the
BACnet Device object. The field
Device name
holds the name of the BACnet device object
(property Object_Name).
Important:
The device ID and device name must be unique within the BACnet internetwork.