69
Menu A: Heating
A 6 H E
c O f f 3
4 ° C
Select the cascaded water heaters supply temperature control.
This parameter is the offset of the selected CH
supply temperature of EACH Water heater of the total cascade.
Menu A: Heating
A 7 H E
c P r b 3
2 5 ° C
Select the cascaded water heaters supply temperature control.
This parameter is the proportional range of the selected
CH supply temperature of EACH Water heater of the total
cascade and of the external (cascade) sensor.
Menu A: Heating
A 8 H E
c l n t 3
8 0 S e c
Select the cascaded water heaters supply temperature control.
This parameter is the integration time of the selected
CH supply temperature of EACH Water heater of the total
cascade and of the external (cascade) sensor.
Menu A: Heating
A 9 T i m e r C o n t
0
Function to activate "external time controller":
0 = Off
1 = On
Connect to 13-14. Contact closed = daytime setting,
Contact open = night-time setting.
Menu B: Hot water
B 1 D H i p m p / t w v
1
Hot water function of the Water heater by:
0 = pump
1 = 3-way valve
Menu B: Hot water
B 2 D H i f l o w L O
2 5 ° C
Hot water function of the Water heater. This parameter is the
CH supply temperature LOW level with an indirect
hot water demand.
Menu B: Hot water
B 3 D H i f l o w H I
8 5 ° C
Hot water function of the Water heater. This parameter is the
CH supply temperature HIGH level with an indirect
hot water demand.
The Screen Text on these pages show
Parameters used on our EF water heater and
also our CPM Boilers. Certain functions may
not apply to the appliance you are working
on. If there is any doubt contact Lochinvar
Limited.