DJUSTMENT VALUES
To make adjustments easier, values of table 1 are presented in the following figures.
The CO
2
/ O
2
values should always be between the values set in this figure. Nominal values can be found in the
Technical specifications datasheet at the beginning of this manual. All values are measured without front door.
21.2.1
Gas type G20
The CO
2
level must not be in the hatched area.
EF80 - EF180
____________________________________________________________________________
21.2.2
Propane G31:
Fan settings must be changed by altering parameter P4BD (display D8). (Only by a Competent Engineer).
The CO
2
level must not be in the hatched area.
EF80 - EF120
adjust
adjust
adjust
adjust
max load
min load
4.5 %
4.8 %
5.4 %
5.7 %
O
2
9.2 %
9.0 %
8.7 %
8.5 %
CO
2
adjust
adjust
adjust
adjust
max load
min load
4,9 %
5,2 %
6,7 %
7,0 %
O
2
10,5 %
10,3 %
9,3 %
9,1 %
CO
2
O.K.
O.K.
O.K.
O.K.