48
SENSOR
SENSOR TYPE
SENSOR VALUE
S1
Internal flow sensor
NTC-10K
S2
Internal return sensor
NTC-10K
S3
Tank sensor
NTC-10K
S6
Flue gas sensor
NTC-10K
11.2.2
Senor values
Temperature
(°C)
Resistance
(Ω)
Temperature
(°C)
Resistance
(Ω)
Temperature
(°C)
Resistance
(Ω)
Temperature
(°C)
Resistance
(Ω)
-30
175203
20
12488
70
1753
120
387
-25
129289
25
10000
75
1481
125
339
-20
96360
30
8059
80
1256
130
298
-15
72502
35
6535
85
1070
135
262
-10
55047
40
5330
90
915
140
232
-5
42158
45
4372
95
786
145
206
0
32555
50
3605
100
677
150
183
5
25339
55
2989
105
586
155
163
10
19873
60
2490
110
508
160
145
15
15699
65
2084
115
443
165
130
11.2.3
Conversion table temperature vs resistance for all sensors
F
USES
The E
CO
F
ORCE
™ has four internal fuses. Three will automatically reset, the fourth is rated at 3.15 A, and is located at the rear of the main
control board.
A
RC
W
ELDING
P
RECAUTIONS
The appliance must be isolated from the mains electricity supply in the event of electric arc welding being carried out on any connecting
pipework.
Summary of Contents for EcoForce EF100
Page 2: ...2 ...
Page 24: ...24 ...
Page 25: ...25 ...
Page 26: ...26 ...
Page 30: ...30 ...
Page 31: ...31 ...
Page 32: ...32 ...
Page 33: ...33 ...
Page 119: ...119 ...
Page 120: ...120 ...