20
C13,
C33
C
ONCENTRIC
F
LUE
S
YSTEMS
C
13
FLUE SYSTEM SPECIFICATION
MANUFACTURER MUELINK & GROL
TEMPERATURE CLASS T120
FLUE GAS MATERIAL PP
EACH HORIZONTAL CONCENTRIC FLUE ASSEMBLY IS SUPPLIED WITH THE FOLLOWING ITEMS:
CONCENTRIC WALL TERMINAL
WALL PLATES
90° BEND
ADDITIONAL FLUE ITEMS ARE AVAILABLE SEE FLUE ASSEMBLY AND ANCILLARIES GUIDE AT
WWW.LOCHINVAR.LTD.UK
8.6.1
C
13
horizontal concentric flue system components
Model
Description
Flue Assembly Item number
EF80
Horizontal Concentric flue kit 80/125mm
EFHF002
EF100
Horizontal Concentric flue kit 100/150mm
EFHF004
EF120
Horizontal Concentric flue kit 100/150mm
EFHF004
EF150
Horizontal Concentric flue kit 130/200mm
EFHF005
EF180
Horizontal Concentric flue kit 130/200mm
EFHF005
8.6.2
C
13
horizontal concentric flue assemblies
8.6.3
Horizontal terminal installation
When the heater is installed as a Type C
13
appliance, the flue system should be installed as follows:
1.
Determine the location of the flue terminal, taking into account minimum distances as detailed in Section 8.3.1 and the relevant
British Standards.
2.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The diameter of the hole should be no
more than 10mm greater than the diameter of the air supply pipe of the terminal.
3.
Determine the required length of the terminal and cut as necessary.
NOTE: When determining the required length for the flue terminal, the outer wall plate or rosette should be flush to the wall. See
Section 8.6.4
NOTE: Once cut; remove all burrs and sharp edges.
4.
Insert the terminal into the drilled hole. The terminal section should be installed level or with a fall to outside (Max. 10 mm per metre)
to prevent the ingress of water.
NOTE: When inserting the terminal, ensure the air intake section is at the bottom.
5.
Fill the void between the terminal and wall with water resistant sealant.
6.
Fit the wall plates or rosette using appropriate fixings.
7.
Install the remainder of the flue system working progressively away from the Water heater supporting the pipes as necessary.
8.6.4
Installation of concentric terminal
Summary of Contents for EcoForce EF100