70
The Screen Text on these pages show
Parameters used on our EF water heater and also
our CPM Boilers. Certain functions may not apply
to the appliance you are working on. If there is any
doubt contact Lochinvar Limited.
Menu B: Hot water
B 4 D H i L O t i m e
1 M i n
Hot water function of the Water heater. This parameter is the
selectable time period after which the Water heater switches
from LOW to HIGH set point with an indirect hot water
demand.
Menu B: Hot water
B 5 L e g i o t e m p
8 5 ° C
Pasteurisation function of the Water heater. This parameter is the
selected hot water temperature during the pasteurisation
function of the Water heater.
Menu B: Hot water
B 6 L e g i o h y s t
2 ° C
Pasteurisation function of the Water heater. This parameter is the
selected hysteresis during the pasteurisation
function of the Water heater.
Menu B: Hot water
B 7 L e g i o h o l d
2 M i n
Pasteurisation function of the Water heater. This parameter is the
selected time period for the pasteurisation
function of the Water heater.
Menu B: Hot water
B 8 L e g i o i n t r
0
Pasteurisation function of the Water heater. This parameter
controls if the CH demand can be interrupted by the
pasteurisation function of the Water heater.
0 = Yes
1 = No
Menu B: Hot water
B 9 D H d s c O f f 2
4 ° C
Function for the direct hot water Water heater.
This parameter is de off set of the selected HW
temperature of the Water heater.
Menu B: Hot water
B A D H d s c P r b 2 3
2 0 ° C
Function for the direct hot water Water heater.
This parameter is the proportional range of the selected
HW temperature of the Water heater.