For All Installations
LEDs — Detailed Descriptions
Power LED
This LED indicates that the LNI 2000 is powered. It will light when the unit is
plugged into a 120 VAC outlet or is powered from the 12 V DC alarm panel
feed. The blinking “heartbeat” of three seconds on, one second off indicates
normal operation.
If the power LED remains dark even though the unit is powered, or continuously
on for more than two minutes, replace the LNI 2000 with a new one.
IP Link LED
This LED indicates the presence of a valid connection between the LNI 2000
and the central station LNS over the Internet.
Automatically obtained an IP address
When the LNI 2000 first starts up, this LED will flash on a 1 second flash cycle
until the unit has obtained an IP address from the customer’s network.
The LED will then turn on and stay lit. This signifies that the LNI is connected
to the LNS at the central station. If the LED fails to light, the unit is improperly
configured to connect to the central station, or there is a problem with the
network/Internet connection preventing connection to the LNS.
If the LED flashes for more than 30 seconds, it has been unable to obtain an IP
address automatically from the customer’s router.
Static IP Address
If the LNI 2000 is configured with a static IP address, the IP Link LED will light
signaling that a successful connection to the LNS at the central station was
made, or stay unlit signaling that it has failed to connect.
No connection to central station
If the IP Link LED stays off for more than 10 seconds, the LNI 2000 was not
able to connect to the central station LNS. There are four possible reasons for
this failure.
An incorrect destination IP address may have been entered while
programming the LNI 2000;
LoBenn Network Interface 2000 Installation Manual
62