Note
: Use These Instructions for
Standard
Installations
7. Verify that the IP Link and IP Monitoring LEDs relight and the central
station has received a restoration alarm.
Communication Trouble Alarm Test Two
1. Disconnect the LNI 2000 from the alarm panel by unplugging the alarm
cable from the “Panel” port.
2. After the programmed communication trouble alarm time has elapsed, the
IP Monitoring LED will stay on and the central station will receive a
communication trouble alarm.
3. Verify that the test alarm (if applicable) and the “Communication Trouble
Alarm” are received correctly at the central station.
4. Reconnect the alarm cable removed in Step 1.
5. Verify that the Link and IP Monitoring LEDs are still on and that the
central station has re-established connection and received a restoration
alarm.
Note
: The programmed Communication Trouble Alarm Time (CTAT)
may be too long for a convenient testing of this capability. (ULC
installations must not exceed a
maximum
CTAT of 90 seconds.) If
this is the case, conduct Communication Trouble Alarm Tests One
and Two as described but limit the required verifications to:
1. Verify that the central station receives the test alarm from the
alarm system keypad (if applicable).
2. Verify that the central station has received a restoration alarm
upon reconnection of the LNI 2000.
LNI 2000 Installation Manual