- 98 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Display
code
Title
Cause of error
Check point & Normal condition
41
D-pipe sensor (Inverter)
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
44
Air sensor
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
45
Condenser Mid pipe sen-
sor
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
46
Suction Pipe sensor
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
47
Const-D-Pipe Sensor Error
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
114
Injection In Sensor Error
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
115
Injection Out Sensor Error
• Open / Short
• Soldered poorly
• Internal circuit error
1. Bad connection of thermistor connector
2. Defect of thermistor connector (Open/Short)
3. Defect of outdoor PCB(Inverter)
Check Point
1. Estimate the resistance of each sensor.(Unplugged)
2. Check the value of the resistor of thermistor.
D-pipe sensor (Inverter)
: Normal Value of the resistor is 200kΩ at 25℃
Air sensor
: Normal Value of the resistor is 10kΩ at 25℃
Cond. Mid-pipe sensor
: Normal Value of the resistor is 5kΩ at 25℃
Suction pipe sensor
: Normal Value of the resistor is 5kΩ at 25℃
Condenser Out-pipe sensor
: Normal Value of the resistor is 5kΩ at 25℃
Is sensor connected to
PCB(Inverter) correctly?
Is sensor value correct?*
Connect sensor to PCB(Inverter)
correctly
Replace sensor
Replace corresponding
PCB(Inverter)
Yes
No
No
Yes
n
Error Diagnosis and Countermeasure Flow Chart