Error Diagnosis and Countermeasure Flow Chart
PCB assembly 1
Power connection normal?
No
Yes
Is input voltage normal ?
No
Yes
Is PCB(Inverter) Normal?
No
Replace PCB assembly 1
Recheck power and installation
condition
Yes
Check power input voltage
Check power connection state
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Display
code
Title
Cause of error
Check point & Normal condition
23
DC Link Low Volt
• DC Link Voltage is
below 140 V DC
• Check CN_(L), CN_(N) Connection
• Check Input Voltage
• Check PCB DC Link voltage sensor parts
28
DC Link High Volt
• DC Link Voltage is
above 420 V DC
• Check CN_(L), CN_(N) Connection
• Check Input Voltage
• Check PCB DC Link voltage sensor parts