- 83 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
21
DC PEAK
(IPM Fault)
• Instant over current
• Over Rated current
• Poor insulation of IPM
• An instant over current in the U,V,W phase
- Comp lock
- The abnormal connection of U,V,W
• Over load condition
- Overcharging of refrigerant Pipe length.
Outdoor Fan is stop
• Poor insulation of compressor
Display
code
Title
Cause of error
Check point & Normal condition
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor
terminal and pipe
→
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
1. Check inverter PCB assembly 1 U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly 1 IPM normality
→
Replace inverter PCB assembly 1
Is inverter PCB assembly 1 normal?
No
n
Error Diagnosis and Countermeasure Flow Chart
n
Comp checking method
V
U
W
Comp
Copper
pipe
Comp
WARNING
Before checking PCB(Inverter) or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby
state of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.
Model
Windings Resistance (at 75 °C)
ZHBW126A0
ZHBW146A0
ZHBW166A0
U-V
0.845 Ohms
V-W
0.859 Ohms
W-U
0.864 Ohms
Terminal
Insulation Resistance
U-panel
≥ 10MΩ
V-panel
≥ 10MΩ
W-panel
≥ 10MΩ