- 54 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Check to see whether there is any refrigerant leakage, and check whether the power or transmission
cable is connected properly.
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal block and
ground. Do not operate in the case of 2.0 MΩ or less.
NOTE
: Never carry out mega ohm check over terminal control board.
Otherwise the control board may break.
Immediately after mounting the unit or after leaving it turned off for an extended length of
time, the resistance of the insulation between the power supply terminal board and the
ground may decrease to approx. 2.0 MΩ as a result of refrigerant accumulation in the inter-
nal compressor.
If the insulation resistance is less than 2.0 MΩ, turn on the main power supply.
1
2
1. Check before Test Run
3. Test Run
2. Test Run Flow chart
Is cold water discharged for
more than 3 minutes ?
START
Operation mode change
to Heating mode
Operate the unit in heating mode.
Does Test operation start?
Check whether the power cable and
communication cable are completely connected
Yes
No
Yes
No
Is hot water discharged ?
Yes
No
Is there any temperature
difference between intake and
discharged water?
No
Yes
Normal
* Check the load (In/Out Temp.)
* Check pipe length and amount of
refrigerant
* Check for abnormal sound in
* Refer to Troubleshooting Guide
outdoor unit (comp.,Fan, others )