- 74 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Check Point
1. Check the wire connection. (Open / Short)
’
Repair the connection
2. Check the soldering state of connector. (Soldered poorly)
’
Repair or Change the PCB(Heater).
3. Check the volt. Of Main PCB(Heater) power source. (DC 12 V)
’
Repair or Change the Main PCB(Heater).
4. Check the installation of wired remote controller. (Noise interference)
’
Adjust the state of installation
Check the Volt.
Unit
V
12Vdc
12V
(RD)
S
(YL)
S
(YL)
GND
(BK)
Check the Volt.
Wired R/C
V
12Vdc
12V
(RD)
GND
(BK)
Check the wire
connection(Open /
Short / Miswirring)
Is it normal ?
Check the volt. of Main
PCB(Heater) power
source. (DC 12V,DC 5V)
Is the soldering state
of connector is normal?
Yes
Yes
No
Correct connection
Or change connection wire
Is it normal ?
Yes
No
Correct connection
Or change the PCB
Check the installation of
wired remote controller.
(Noise interference)
Is it normal ?
No
Adjust the state
of installation
No
Re-soldering component
Or change the PCB
Check Flow Chart
CN_REMO
03
Communication Error
(Wired remote controller)
• Connector connection
error
• Faulty PCB(Heater) /
Remote controller
• Connection wire break
• Connection of wire
• Main PCB(Heater) Volt. DC 12 V
• Noise interference
Display
code
Title
Cause of error
Check point & Normal condition