79
CHAPTER 6 -
PARAMETER DESCRIPTION
6.1 Drive group [DRV]
DRV-00: Command Frequency or Command
Torque/ Output Current (LCD)
* In Torque mode: LCD display - Cmd. Trq
7 Segment - r (Rpm)
l
In FU2-39 [Control Mode Selection], 4
(Sensorless_T) 6 (Vector_TRQ) is torque mode.
l
DRV-00 [Command Frequency or Command
Torque] has two functions.
1)
Digital frequency setting
- When DRV-04 [Frequency or Torque Mode] is set to 0
(KeyPad-1) or 1 (KeyPad-2), command freq is not
settable above FU1-20 [Maximum Frequency].
2)
Monitoring function setting
- Command frequency displayed during stop
- Output current/frequency displayed during run.
Analog/digital frequency command setting in DRV-04
[Frequency or Torque Mode]:
l
DRV-04 [Frequency or Torque Mode] is set to 2
(V1),3 (I) or 4 (V1+I), frequency command is set via
I/O-01~10 [Analog Frequency command/Torque].
Refer to I/O-01~10 for detail description.
l
DRV-16 [Speed Unit Selection] is set to 1 (Rpm),
speed is displayed in Rpm.
l
If FU2-39 is set to 4 (Sensorless_T) or 6
(Vector_TRQ), speed is displayed as the percent
[%] to the rated torque. Torque command is
settable in DRV-04 [Frequency or Torque Mode].
* Factory default setting = 100[%]
(Up to 150[%] settable)
l
Setting the DRV-04 [Frequency or Torque Mode]
☞
Note:
In torque mode, speed unit is automatically
displayed in [%].
Setti
ng
DRV-04
Parameter
Name
Programming Description
0
KeyPad-1
1. In DRV-00, press the [PROG]
key. 2. Enter the desired freq. 3.
Press the [ENT] key to write the
new value into memory.
1
KeyPad-2
Digital freq.
command
1. In DRV-00, press the [PROG]
key. 2. Press the [
ñ
(Up)] or
[
ò
(Down)] key to set the desired
freq., while the inverter keeps
running. 3. Press the [ENT] key
to write the new value into
memory.
2
V1
Control terminal “V1” Voltage
analog input (0 to 10V)
See the description of I/O-01~05.
3
I
Control terminal “I” Current
analog input (4 to 20mA)
See the description of I/O-06~10.
4
V1+I
Analog
freq.
command
Control terminal “V1”+“I”
(0-10V/4-20mA) Analog input.
See the description of I/O-01~10.
l
Command Freq/Torque setting via “V1” input
terminal when set DRV-04 [Frequency/Torque
mode] to 2 (V1) or 4 (V1+I)
Code
Default setting
Setting range
I/O-01
10 [msec]
0 ~ 10000 [msec]
I/O-02
0 [V]
0 ~ 10 [V]
I/O-03
0 [Hz]
0 ~ Max. freq
I/O-04
10 [V]
0 ~ 10 [V]
I/O-05
60 [Hz]
0 ~ Max freq
DRV? Cmd. Freq*
00 0.00 Hz
0.00
F *
Factory Default:
0.00 Hz
0.00