Chapter 6 - Parameter Description [APP]
147
☞
The ‘Trv Acc’ terminal set in EXT-30 to EXT-32 is ON
during traverse acceleration time. (Open Collector
Output)
☞
The ‘Trv Dec’ terminal set in EXT-30 to EXT-32 is ON
during traverse deceleration time. (Open Collector
Output)
☞
APP-04 and APP-05 should be set to a value less than
APP-03. If not, traverse control does not accomplished
correctly.
APP-06: Traverse Offset (Hi) Setting
APP-07: Traverse Offset (Lo) Setting
This code makes positive offset during traverse
operation by multi-function input terminal. When the ‘Trv
Off Hi’ terminal is ON, the offset frequency is added to
the reference frequency. To use this function, set a
terminal out of multi-function input terminals (P1, P2, P3)
to ‘Trv Off Hi’ in I/O-12 ~ I/O-14. The offset value is
determined by,
Trv. Off Hi Frequency =(Reference Frequency * Trv. Off
Hi)/100
This code makes negative offset during traverse
operation by multi-function input terminal. When the ‘Trv
Off Lo’ terminal is ON, the offset frequency is subtracted
from the reference frequency. To use this function, set a
terminal out of multi-function input terminals (P1, P2, P3)
to ‘Trv Off Lo’ in I/O-12 ~ I/O-14. The offset value is
determined by,
Trv. Off Lo Frequency =(Reference Frequency * Trv. Off
Lo)/100
APP-08: Running Auxiliary Motor Number
Display
This code shows how many auxiliary motors are running
by MMC control.
APP-09: Starting Auxiliary Motor Selection
This code sets the starting auxiliary motor for MMC
control.
APP-10: Operation Time Display on Auto
Change
This code displays the operation time after Auto Change
is accomplished.
APP-11: Start Frequency of Aux. Motor 1
APP-12: Start Frequency of Aux. Motor 2
APP-13: Start Frequency of Aux. Motor 3
APP-14: Start Frequency of Aux. Motor 4
The inverter turns on AUX, RLY1, RLY2, and RLY3 in
APP? Trv Off Hi
06 0.0 %
0.0
06
Factory Default:
0.0 %
0.0
APP? Trv Off Lo
07 0.0 %
0.0
07
Factory Default:
0.0 %
0.0
APP?Aux Mot Run
08 0
0
08
Factory Default:
0
0
APP?Starting Aux
09 1
1
09
Factory Default:
1
1
APP?Auto Op Time
10 00:00
00:00
10
Factory Default:
00:00
00:00
APP?Start freq1
11 49.99 Hz
49.99
11
Factory Default:
49.99 Hz
49.99
APP?Start freq2
12 49.99 Hz
49.99
12
Factory Default:
49.99 Hz
49.99
APP?Start freq3
13 49.99 Hz
49.99
13
Factory Default:
49.99 Hz
49.99
APP?Start freq4
14 49.99 Hz
49.99
14
Factory Default:
49.99 Hz
49.99