Chapter 6 - Parameter Description [I/O]
130
[AXA-AXC configured as ‘FDT-3’]
[FDT-4]
AXA-AXC is CLOSED when the output frequency
reaches the FDT frequency. The output is OPENED
when the output frequency goes below the FDT
bandwidth centered on the FDT frequency.
[AXA-AXC configured as ‘FDT-4’]
[FDT-5]
This is the inverted output of [FDT-4].
[AXA-AXC configured as ‘FDT-5’]
[OL]
AXA-AXC is CLOSED when the output current has
reached the FU1-54 [Overload Warning Level] for the
FU1-55 [Overload Warning Time].
[AXA-AXC configured as ‘OL’]
[IOL]
AXA-AXC is CLOSED when the output current is above
the 150% of rated inverter current for 36 seconds. If this
situation is continued for one minute, the inverter will cut
off its output and displays ‘IOL’ (Inverter overload) Trip.
See the nameplate for the rated inverter current.
[AXA-AXC configured as ‘IOL’]
AXA-AXC
ON
Output Frequency
Time
Time
I/O-43 / 2
ON
I/O-42
AXA-AXC
Output Frequency
Time
Time
I/O-43 / 2
CLOSED
I/O-42
AXA-AXC
Output Frequency
Time
Time
I/O-43 / 2
ON
I/O-42
ON
Related Functions:
FU1-54 [Overload Warning Level]
FU1-55 [Overload Warning Time]
t1: FU1-55 [Overload Warning Time]
Output Current
Time
Time
FU1-54
[OL level]
FU1-54
[OL level]
AXA-AXC
ON
t1
t1
Output Current
Time
Time
150% of Rated
Inverter Current
AXA-AXC
ON
36sec
150% of Rated
Inverter Current
24sec