Chapter 5 - Parameter List
64
5.4 Input/Output Group [I/O]
Keypad Display
Setting Range
Code
Description
LCD
7-Segment
LCD
7-Segment
Units
Factory
Default
Adj.
During
Run
Page
I/O-00
Jump to Desired Code #
Jump code
Not displayed
1 to 99
Not available
1
1
Yes
118
I/O-01
Filtering Time Constant
for V1 Signal Input
V1 filter
01
0 to 9999 [ms]
1
10 [ms]
Yes
I/O-02
V1 Input Minimum
Voltage
V1 volt x1
02
0 to 10 [V]
0.01
0.00 [V]
Yes
I/O-03
Frequency
Corresponding to V1
Input Minimum Voltage
V1 freq y1/
V1 [%] y1
03
0 to FU1-20 [Hz]/
0-150 [%]
0.01
0.0 [Hz]/
0[%]
Yes
I/O-04
V1 Input Maximum
Voltage
V1 volt x2
04
0 to 10 [V]
0.01
10.00 [V]
Yes
I/O-05
Frequency
Corresponding to V1
Input Maximum Voltage
V1 freq y2/
V1 [%] y2
05
0 to FU1-20/
0-150 [%]
0.01
60.00 [Hz]/
100[%]
Yes
118
I/O-06
Filtering Time Constant
for I Signal Input
I filter
06
0 to 9999 [ms]
1
10 [ms]
Yes
I/O-07
I Input Minimum Current
I curr x1
07
0 to 20 [mA]
0.01
4.00 [mA]
Yes
I/O-08
Frequency
Corresponding to I Input
Minimum Current
I freq y1/
I [%] y1
08
0 to FU1-20
0-150 [%]
0.01
0.0 [Hz]/
0[%]
Yes
118
I/O-09
I Input Maximum Current
I curr x2
09
0 to 20 [mA]
0.01 20.00 [mA] Yes
I/O-10
Frequency
Corresponding to I Input
Maximum Current
I freq y2/
I [%] y2
10
0 to FU1-20/
0-150 [%]
0.01
60.00 [Hz]/
100[%]
Yes
118
None
0
half of x1
1
I/O-11
Criteria for Analog Input
Signal Loss
Wire broken
11
below x1
2
-
None
Yes
119
Speed-L
0
Speed-M
1
Speed-H
2
XCEL-L
3
XCEL-M
4
XCEL-H
5
Dc-brake
6
2nd Func
7
Exchange
8
- Reserved -
9
Up
10
Down
11
3-Wire
12
Ext Trip-A
13
Ext Trip-B
14
iTerm Clear
15
Open-loop
16
I/O-12
Multi-Function Input
Terminal ‘P1’ Define
P1 define
12
Main-drive
17
-
Speed-L
Yes
120