Troubleshooting Guide
- 125 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1.Loose connection of power cable/communi-
cation cable(Open/Short)
2.Defect of each outdoor unit PCB
Error No.
Error Type
Error Point
Main Reasons
Master displays ODU number
which is not communicated.
Slave displays own error number
Transmission Error
Between Outdoors
104*
Master
11
→
041
Slave
12
→
042
■
Error Diagnosis and Countermeasure Flow Chart
Is communication
cable installed
normally?
Connect communication cable
Yes
No
Is Slave Unit Dip SW
setting done?
Yes
Dip SW setting
No
* Slave Unit Dip SW
Slave
Is main PCB power
supplied?
Yes
Connect power cable
No
Replace main PCB
1
2
3
4
5
6
7
ON
1
2
3
4
5
6
ON
1
2
3
4
5
6
7
8
9 10 11 12 13 14
Summary of Contents for ARUN Series