Inverter PCB Assy IPM
Fault occur
Error
No.
Error Type
Error Point
Main Reasons
IPM self protection circuit
activation
(Overcurrent/IPM overheat-
ing/Vcc low voltage)
1.Over current detection at Inverter compres-
sor(U,V,W)
2.Compressor damaged (insulation dam-
aged/Motor damaged)
3.IPM overheating
(Heat sink fan damaged/Heat sink fan con-
nector disconnected/Heat sink disassem-
bled)
4.Inverter compressor terminal disconnected
or loose
5.Inverter PCB assembly damaged
6.ODU input current low
■
Error diagnosis and countermeasure flow chart
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Recheck power and installation condition
Yes
1. Check resistance between each terminal of compressor
(refer to page 63)
2. Check insulation resistance between compressor
terminal and pipe (over 50M
Ω
)
→
Replace compressor if abnormality found
Is inverter PCB assembly
normal?
No
Check inverter PCB assembly IPM normality.
→
Replace inverter PCB assembly if abnormality found.
Is compressor
Wire connection
condition normal?
No
1.Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
Yes
Yes
Is inverter heat sink
cooling fan normal?
No
1. Check heat sink cooling fan connector connection
condition
2. Check heat sink cooling fan wire disconnection and
wiring
→
Reassemble and change wire if abnormality found
3. Check heat sink cooling fan output voltage during
compressor operation
(Check main PCB assembly CN15 fan connector output
voltage : AC 220V)
→
Replace main PCB if output voltage isn't AC 220V
4. Check heat sink cooling fan motor wire disconnection
(measure resistance between each ends of motor
connector)
(measured value should be within 1.7k
Ω
±
10%)
→
Replace fan motor if motor wire is disconnected.
21*
Master
211
Slave
212
Summary of Contents for ARUN Series