Self-diagnosis function
Pressure unbalance between outdoor units
Pressure unbalance between outdoor units
Comp locking, Check Valve leakage, comp dielectric
break down at Master Outdoor Unit
Comp locking, Check Valve leakage, comp dielectric at
Slave Outdoor Unit
Liquid pipe temperature sensor of Master outdoor unit
is open or short
Liquid pipe temperature sensor of Slave outdoor unit is
open or short
Master Outdoor Unit Subcooling Inlet Temperature
Sensor open or short
Slave Outdoor Unit Subcooling Inlet Temperature
Sensor open or short
Master Outdoor Unit Subcooling Outlet Temperature
Sensor open or short
Slave Outdoor Unit Subcooling Outlet Temperature
Sensor open or short
Master Outdoor Unit Fan DC Link Input Voltage is
under 380V
Slave Outdoor Unit Fan DC Link Input Voltage is under
380V
Master Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
Slave Outdoor Unit Fan Inverter PCB Temperature is
Over 95°C
Master Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
Slave Outdoor Unit Fan PCB Heat Sink Temperature
Sensor open or short
Failure of operation mode conver-
sion at Master Outdoor Unit
Failure of operation mode conver-
sion at Slave Outdoor Unit
Master Outdoor Unit Constant
Speed Compressor Fault
Slave Outdoor Unit Constant
Speed Compressor Fault
Master Outdoor Unit Liquid pipe
Temperature Sensor Error
Slave Outdoor Unit Liquid pipe
Temperature Sensor Error
Master Outdoor Unit Subcooling
Inlet Temperature Sensor Error
Slave Outdoor Unit Subcooling
Inlet Temperature Sensor Error
Master Outdoor Unit Subcooling
Outlet Temperature Sensor Error
Slave Outdoor Unit Subcooling
Outlet Temperature Sensor Error
Master Outdoor Unit Fan DC Link
Low Voltage Error
Slave Outdoor Unit Fan DC Link
Low Voltage Error
Excessive increase of Master
Outdoor Unit Fan PCB Heat Sink
Temperature
Excessive increase of Slave
Outdoor Unit Fan PCB Heat Sink
Temperature
Master Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Slave Outdoor Unit Fan PCB
Heat Sink Temperature Sensor
Error
Display
Title
Cause of Error
1
1 5
1
2
1
1 7
3
2
1
1 9
3
2
1
1 9
4
2
Outdoor unit related error
1
1
1
3
2
1
1
1
4
2
1
1
1
5
2
1
1 0
7
2