4.11 Vacuum Mode
This function is used for creating vacuum in the system after compressor replacement, ODU parts replacement
or IDU addition/replacement.
4.12 Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan
discharge of ODU.
■
Static pressure compensation dip S/W setting method
High static pressure mode (Max. RPM 930) : Master ODU Main PCB SW02B NO.13 Dip S/W
Low static pressure mode (Max. RPM 900) : Master ODU Main PCB SW02B NO.12 Dip S/W
Master Main PCB D/W ON ( No.11,14)
Vacuum mode setting
ODU V/V OPEN
Main Lev, SC Lev OPEN
IDU Lev OPEN
ODU power reset
Press the black button Main PCB (5 sec.)
Main PCB
SW01S
Main PCB
SW02B
Main PCB
SW01V
ODU operation stops during vacuum mode. Compressor can't operate.
Vacuum mode setting method
Vacuum mode cancellation method
Master Main PCB D/W OFF( No.11,14)
Power Reset
Vacuum Mode cancellation
Power Reset
Dip SW setting
High static pressure:No. 13
Low static pressure:No.12
Static pressure compensation mode setting
method
Static pressure compensation mode cancellation
method
Dip SW OFF
Power Reset
Static pressure compensation mode is set
Static pressure compensation mode is cancelled
Caution
Function