Troubleshooting Guide
- 110 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Main PCB defect
2. No power of R,S,T supplied
3. Wring connection of R,S,T cables
4. Main Pcb Fuse failure
Error
No.
Error Type
Error Point
Main Reasons
Wrong connection of 3Ø
power supply cable
(Reverse direction / miss-
ing a phase)
Wrong connection of 3Ø
power supply cable
(Reverse direction / missing
a phase)
54*
Master 541
Slave 542
■
Error diagnosis and countermeasure flow chart
Yes
Is main PCB fuse normal?
No
Replace Fuse
Is CH 54 occurred again
after reset MAIN
circuit breaker?
No
End
Yes
Is connection and phase
order of power cables to main /
slave outdoor unit correct?*
No
Connect correctly
Is connection and phase
order of power distribution
panel correct?**
No
Connect power cables in
distribution panel correctly
Yes
Yes
Replace main PCB
Summary of Contents for ARUN Series
Page 134: ...P NO MFL50459503 MAY 2008 ...