Troubleshooting Guide
- 106 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
50*
Master
501
Slave
502
ODU 3phase power omis-
sion error
Error
No.
Error Type
Error Point
Main Reasons
Omitting one or more of
R,S,T input power
1. Input Voltage abnormal (R,S,T)
2. Check power Line connection condition
3. Main PCB damage
■
Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
No
Yes
Recheck power and installation condition
Check
R~S/S~T/T~R Phase voltage : 460V
±
10% (3Ø 460V)
208/230V
±
10% (3Ø 208/230V)
→
Check connection condition and wiring if power is
abnormal
Is main PCB assembly normal?
No
Yes
Replace Main PCB assembly
* Measuring input voltage
* Noise filter wiring
* Main PCB power connection
T
S
R
T
S
R
Summary of Contents for ARUN Series