Checking Method for Key Components
2.5 Inverter IPM Checking Method
1. Wait until inverter PCB DC voltage is discharged after main power off.
2. Pull out CN-P1, CN-N1 connectors and U,V,W COMP connector connected with the inverter PCB.
3. Set multi tester to resistance mode.
4. If the value between P and N terminal of IPM is short(0
Ω
) or open(hundreds M
Ω
), PCB needs to be
replaced.(IPM damaged)
5. In the measured value with resistance mode should be within 28K
Ω
±10%.
6. In case measured value is different from the table, PCB needs to be replaced.(PCB damaged).
✽
Red(+) and black(-) are the measuring terminals of multi tester.
P terminal : black (-)
N terminal : red (-)
U terminal : red(+)
28K
Ω
± 10%
Open
V terminal : red(+)
28K
Ω
± 10%
Open
W terminal : red(+)
28K
Ω
± 10%
Open
P terminal : red(+)
N terminal : red (+)
U terminal : black(-)
Open
28K
Ω
± 10%
V terminal : black(-)
Open
28K
Ω
± 10%
W terminal : black(-)
Open
28K
Ω
± 10%
U terminal
V terminal
W terminal
P terminal
N terminal
CN-N1
CN-P1
3Ø 460V
3Ø
208/230V
U terminal
V terminal
W terminal
U,V,W connector
N terminal
P terminal