Troubleshooting Guide
- 132 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Constant compressor damage
2. Constant compressor input over
current
3. Discharge temperature sensor defect
Error No.
Error Type
Error Point
Main Reasons
Defect according to constant
compressor damage or lock-
ing, over current
Constant compressor
defect
173*
Master
11
→
731
Slave
12
→
732
■
Error diagnosis and countermeasure flow chart
Is resistance value
(insulation & phase to phase)
of corresponding constant
compressor normal ?
[refer electric
component part]
No
Replace constant compressor
Is discharge temperature
sensor of compressor
normal? [refer electric
component part]
No
Is cables
’
connection
of compressor normal?
*
Yes
Adjust connection of cables
No
Replace discharge
temperature sensor
Yes
Yes
Replace outdoor unit PCB
* cables connection between constant
compressor and magnetic switch