Troubleshooting Guide
- 121 -
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1.Fan motor hall sensor defect
2.ODU fan motor hall sensor discon-
nection
3.ODU Fan Motor Hall Sensor wrong
insertion
4.Fan PCB assembly defect
Error No.
Error Type
Error Point
Main Reasons
Fan Motor Hall Sensor short/open
Fan Motor Hall Sensor
Error
78*
Master 781
Slave 782
■
Error Diagnosis and Countermeasure Flow Chart
Check ODU fan motor assemble condition and locking
→
Reassemble or replace if abnormality found
Recheck f an motor hall sensor connection
→
Reassemble if abnormality found
Yes
No
Yes
No
Yes
Is fan motor assemble
condition normal?
Is wiring between fan motor
and PCB normal?
Is connector color between
Hall Sensor PCB matched?
No
Check if connector color matched between fan motor hall sensor and PCB
→
Reassemble if abnormality found
Yes
Is fan PCB assembly normal?
Recheck power and
installation condition
No
Hall sensor connection
Fan motor wire connection
Replace Fan PCB assembly
❈
Note : If LED is blinking oppositely after connecting Hall Sensor connector,
U.V.W output terminal oppositely, replace the motor.
If LED is not blinking oppositely,replace fan PCB assembly.