26
ENGLISH
USING THE PROGRAM
NOTES
y
2Set Auto Mode function is only available for the U.S.
y
This function is activated only when Auto Mode Option is 2Set Auto Mode(US Only Option) and
IDU, ODU supports 2set function. (For further information about whether the device supports
the 2set function, please refer to the device’s manual.)
y
Under 2Set Auto mode, operation mode(cool, heat) status of the actual product is displayed
along with Auto icon.
NOTES
y
ACS IV Controllers’s control command is above the occupancy sensor connected to the IDU.
y
When Occupancy is changed, Cooling Set Temp, Heating Set Temp is changed to the recent
Schedule’s Set Temp. If there was no schedule, Cooling Set Temp, Heating Set Temp is set to
the default.
(Example)
When the schedules were set up as follows,
09AM – 12 PM: Occupied
/ Cooling Set Temp 80°F / Heating Set Temp 64°F
12PM – 13 PM: Unoccupied
/ Cooling Set Temp 84°F / Heating Set Temp 60°F
13PM – 15 PM: Occupied
/ Cooling Set Temp 78°F / Heating Set Temp 66°F
after 15PM
if the room is occupied, Cooling Set Temp is 78°F and Heating Set Temp 66°F.
If the room is unoccupied, Cooling Set Temp is 84°F and Heating Set Temp 60°F.
y
IDU can be set to Occupied ON, Occupied OFF, Unoccupied ON & Unoccupied OFF. When
IDU is controlled OFF neither Heating, Cooling or Fan operation can occur.