114
ENGLISH
USING THE PROGRAM
•
AO
Item
Description
Icon Type
Select a icon type
Unit Name
(20 Characters)
Enter the device name.
y
Up to 20 characters.
Address
It is automatically input according to Exp.I/O address, and it cannot be
changed.
Use
Select device usage
y
Number information: temperature, humidity, open, level, operation
ratio, concentration, pressure
Unit Symbol*
Select unit symbol
y
It is automatically selected according to the usage selection.
I/O Type
Dedicated VOL
Min.*
Input minimum value
y
You can input up to 5 digits
Max.*
Input maximum value
y
You can input up to 5 digits (Maximum two step AO output)
Range*
Select signal output required 0-10 or 2-10 VDC.
Correction*
Input correction value
y
You can input up to 5 digits
Enable
During Exp.I/O registration, 14 Points are available for registration, the
enable check box must be selected to enable use.