- 68 -
26
(261)
Inverter compressor starting
failure Error
Error
No.
Error Type
Error Point
Main Reasons
Starting failure because of
compressor abnormality
1. Overload operation
(Pipe clogging/Covering/EEV defect/Ref.
overcharge)
2. Compressor damage
(Insulation damage/Motor damage)
3. Compressor wiring fault
4. ODU inverter PCB damage (CT)
n
Error Diagnosis and Countermeasure Flow Chart
Is installation
condition normal?
No
Yes
Yes
Recheck power and installation condition
1. Check Pipe clogging/distortion
2. Check Covering (Indoor/Outdoor Unit)
3. Check EEV connector assemble condition/normal
operation
4. Check refrigerant pressure
→
Reassemble or manage if abnormality found
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor
terminal and pipe (over 50 M)
→
Replace compressor if abnormality found
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
No
Yes
1. Check inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
Is compressor
Wire connection
condition normal?
No
Yes
Check inverter PCB assembly IPM normality
→
Replace inverter PCB assembly
Is inverter PCB assembly normal?
No
Are there any power wire
connections normal?
1. Check R/S/T wiring conditions
→
Rewire them if abnormality found.
Measuring resistance between
each terminal of compressor
*Compressor wire connection
Compressor
JQC068MA*
Temp.
U-V
V-W
W-U
25℃
0.216 ± 7% Ω
0.216 ± 7% Ω
0.216 ± 7% Ω
75℃
0.258 ± 7% Ω
0.258 ± 7% Ω
0.258 ± 7% Ω
Error code check