- 61 -
Error code check
Inverter PCB Assy. IGBT
Fault occur
Error
No.
Error Type
Error Point
Main Reasons
IPM self protection circuit
activation
(Overcurrent/IPM overheat-
ing/Vcc low voltage)
1.Over current detection at Inverter compres-
sor(U,V,W)
2.Compressor damaged (insulation dam-
aged/Motor damaged)
3.IPM overheating
(Heat sink disassembled)
4.Inverter compressor terminal disconnected
or loose
5.Inverter PCB assembly damaged
6.ODU input current low
n
Error diagnosis and countermeasure flow chart
Are the resistance
Between each phase and
insulation resistance of Inverter
compressor normal?
No
Yes
Recheck power and installation condition
Yes
1. Check resistance between each terminal of compressor
2. Check insulation resistance between compressor
terminal and pipe (over 50M )
→
Replace compressor if abnormality found
Are there any power wire
connections normal?
No
Yes
1. Check R/S/T/N Wiring Condition
→
Rewire them if abnormality found
Is Inverter PCB assembly
normal?
No
Check Inverter PCB assembly IPM normality.
→
Replace Inverter PCB assembly
if abnormality found.
Is compressor
Wire connection
condition normal?
No
1.Check Inverter PCB assembly U,V,W connector
connection condition
2. Check wire disconnection and wiring
3. Check compressor terminal connection condition
(bad contact)
→
Reassemble if abnormality found
1.Check Inverter PCB assembly P,N connector
connection condition
2.Check wire disconnection and wiring
→
Reassemble if abnormality found
Yes
Yes
Is DC_Link Wire connection
condition normal?
No
1.Check Inverter PCB assembly Comp IPM heat sink
joining condition
→
Reassemble if abnormality found
Yes
Is Comp IPM heat sink’s
joining condition normal?
No
21*
Compressor
JQC068MA*
JQC048MA*
Temp.
25℃
75℃
25℃
75℃
U-V
0.216 ± 7% Ω
0.258 ± 7% Ω
0.302 ± 7% Ω
0.360 ± 7% Ω
V-W
0.216 ± 7% Ω
0.258 ± 7% Ω
0.302 ± 7% Ω
0.360 ± 7% Ω
W-U
0.216 ± 7% Ω
0.258 ± 7% Ω
0.302 ± 7% Ω
0.360 ± 7% Ω