Error code check
- 97 -
Error number
Errors
Meaning
Main cause of occurrence
193
(11
→
931)
Fan board radiator con-
nection temperature
excessive increase
In case where radiator
detection temperature is
more than 95 ℃
1. Radiator temperature sensor abnormality
2. Temperature sensor connector connection defect
3. Fan PCB board defect
194
(11
→
941)
Fan board radiator tem-
perature sensor defect
Radiator temperature sen-
sor abnormality
1. Radiator temperature sensor abnormality
(Open/Short)
2. Temperature sensor connector connection defect
3. Fan PCB board defect
n
Failure diagnosis method
Is a fan motor assembly
status normal?
Confirm fan motor assembly status and restriction
→
Fan motor re-assembly
and replacement when finding a problem
1. Confirm fan motor U,V,W connector connection status
→
Wire
reconnection when finding a problem
2. Confirm a fan motor wire disconnection
→
Outdoor fan motor replacement
when finding a problem
1. Confirm a fan PCB connector connection status
→
Re-assembly and take
action when finding a problem
2. Confirm fan PCB and a radiator connection status
→
Reconnection of the
radiator bolt when finding a problem
Fan PCB board replacement
Confirm fan PCB and a radiator connection status
Is a wire connection of a
fan motor normal?
Is fan PCB assembly status
normal?
Is fan PCB board normal?
Power and installation
environment recheck
Yes
No
No
No
No
Yes
Yes
Yes
Check Screw Connection Condition