Error code check
1.EEPROM bad contact/wrong insertion
2.EEPROM Version is different
3.ODU fan PCB assembly damage
Error No.
Error Type
Error Point
Main Reasons
Error occurs when checking the
EEPROM checksum as initializing
after power is supplied
Fan PCB EEPROM
Error
87
(871)
n
Error Diagnosis and Countermeasure Flow Chart
Is EEPROM insertion normal?
1. Check EEPROM insertion direction/connection condition
2. Check EEPROM checksum
‘ Replace EEPROM if abnormality found
Yes
No
Recheck power and
installation condition
Is Fan PCB assembly normal?
Yes
No
Replace fan PCB assembly
Inverter EEPROM insertion
direction
Same direction both socket
hole and EEPROM hole
❈
Note : Replace after power off
Check IC02L