- 90 -
Error code check
Error number
Errors
Meaning
Main cause of occurrence
105
(11
→
051)
Communication
error (Fan PCB
÷
Inverter PCB)
Fan controller didn't
receive signal from invert-
er controller
1. Wrong connection between Inverter and Fan PCB
2. Fan PCB power not supplied
3. Inv/Fan PCB defect
n
Failure diagnosis method
1. Check DC 15V power cable between Inverter PCB and fan PCB
2. Check communication cable between Inverter PCB and fan PCB
‘ Reconnect or replace wire if abnormality found
Check communication cable between Inverter PCB and fan PCB
‘ Reconnect or replace wire if abnormality found
Yes
No
Yes
No
Is fan PCB communication
LED(yellow) blinking
normally?
Is inverter PCB
communication LED(yellow)
blinking normally?
Yes
Is fan PCB assembly normal?
Recheck power and
installation condition
No
Replace inverter PCB assembly
Fan PCB assembly
Yes
No
Communication Connector
Comp Fan Communication
Connection