- 101 -
Error code check
Sub cooling EEV
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
When operating cooling,
is there a temperature difference of the front
and the rear of Sub cooling EEV?
(In case of EEV open)
When operating
heating, is there a clear
temperature difference of the front and
the rear of over cooling EEV? (In case of EEV
open after securing a discharge
over heating temperature)
No problem EEV over cooling
Check start
Is PCB terminal connection normal?
Terminal
reconnection
PCB replacement
Terminal
reconnection
PCB replacement
Is a signal normally permitted from PCB?
EEV coil check and Sub cooling EEV
replacement
Is PCB terminal connection normal?
Is a signal normally permitted from PCB?
EEV coil check and Sub cooling EEV
replacement